High density, double-conversion on-line power protection with scalable runtime Includes: Smart UPS signalling RS-232 cable, USB cable, User manual Product Overview Automatic restart of loads after UPS shutdown: Automatically starts up the connected equipment upon the return of utility power. Automatic self-test: Periodic battery self-test ensures early detection of a battery that needs to be replaced. Battery failure notification: Provides early-warning fault analysis on batteries enabling timely preventive maintenance ECO Mode: Operating mode that by-passes unused electrical components in good power conditions to achieve high operating efficiency without sacrificing protection LCD Status Display: Provides key UPS status at a glance. Multiple status indicators with load and battery bar graphs. Technical Specifications: Output Max Configurable Power (Watts): 5.0kWatts / 5.0kVA Output Voltage Note: Configurable for 220 : 230 or 240 nominal output voltage Output Voltage Distortion: Less than 2 % Output Frequency (sync to mains): 50/60 Hz +/- 3 Hz Sync to mains Other Output Voltages: 220 V, 240 V Load Crest Factor: 3 : 1 Topology: Double conversion online Waveform type: Sine wave Bypass: Internal bypass (automatic and manual) Input Input frequency: 40 - 70 Hz Auto-sensing Input voltage range for main operations: 160 - 285V Other Input Voltages: 220 V, 240 V Batteries & Runtime Battery type: Lead-acid battery Included Battery Modules: 2 Typical recharge time: 4hour(s) Nominal Battery Voltage: +/- 96 V Expected Battery Life (years): 3 - 5 Battery Charge Power (Watts): 239 Watts Extendable Run Time: 1 Battery Volt-Amp-Hour Capacity: 960